Facility requirements
Facilities must have an appropriately sized and fully functioning grease interceptor. The outflow from the interceptor cannot contain more than 250 mg/L of oil and grease. In-ground interceptors must be pumped out at a minimum of every 30 days. In-floor or under-sink interceptors must be cleaned weekly. Maintenance records on interceptor cleaning and pumping must be maintained for three years and be available on the premises for review.